Hager domovea basic | KNX via Matter | BUILD10
BUILD10
Local Service PartnersAI PartnersProduct
About UsContact
BUILD10
← KNX via Matter catalogProject shortlist (0)
Hager domovea basic TJAS671

Hager

Hager domovea basic

KNX visualization server that exposes selected building devices to Matter over Ethernet.

Product type
KNX to Matter bridge
Model / SKU
TJAS671
KNX connection
Direct KNX TP; KNX ETS or Hager KNX Easy installation
Matter connection
Ethernet

Matter functions & installation

This bridge exposes supported KNX functions to a Matter platform. Its configuration, firmware and supported endpoint types determine which controls and readings are available.

Documented Matter functions

  • Light on/off and dimming
  • Switched sockets
  • Shutter and blind movement
  • Supported thermostats
  • Temperature and humidity sensors
  • Binary inputs

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Bridge setup: commands, readings and feedback

Match the ETS group objects to the selected bridge and receiving app. These examples explain configuration requirements; they do not establish compatibility with every bridge.

Switching and dimming

Configure commands and readable status feedback. 1Home requires absolute brightness values for percentage control; relative wall-button dimming alone is insufficient.

1Home instructions ↗

Shades and blinds

Map movement, stop and position feedback. Slat adjustment needs matching objects. A timed-position fallback estimates position instead of measuring it.

1Home instructions ↗

Climate and sensors

Keep measured temperature and humidity separate from setpoints. A valve output alone is not a complete thermostat. Atios documents the required group addresses for each accessory.

Atios instructions ↗

Extra KNX values

1Home can display generic KNX data in its own app without exporting it to Matter. Do not assume that energy, wind, rain or diagnostic values appear in every Matter app.

1Home instructions ↗

Technical specifications

KNX to Matter · KNX visualization · KNX easy Tool · Local KNX IP tunneling

Matter export capacity
128
Internal KNX / IoT device capacity
500
Parallel Matter ecosystems
3
Matter certificate
CSA250C5MAT45079-00
Certified revision
Hardware 1.0; firmware 1100; Matter 1.1
Commercial status
Current manufacturer-documented model; stock and delivered price not verified.

Sources & limitations

Product research reviewed: Nov 4, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (6)
  • Matter export is limited to 128 KNX devices; the 500-device domovea capacity is a different limit.
  • A Matter controller is required; domovea is not a Matter controller for importing native Matter devices.
  • domovea groups and automations are not exported.
  • The documented export list is narrower than domovea's own visualization features; color lighting and other advanced functions require separate verification.
  • This record applies to TJAS671, not older TJA670 or first-generation TJA450 servers.
  • Exact TJAS671 family documentation and the CSA domovea basic certificate confirm the bridge. Functions must also be supported by the receiving app.
Manufacturer documentation & sources (4)
  • Hager TJAS671/TJAS471 hardware manual and limits ↗Reviewed Nov 4, 2026
  • Hager software manual, section 6.5: Matter device types and export ↗Reviewed Nov 4, 2026
  • Hager Matter prerequisites and limitations ↗Reviewed Nov 4, 2026
  • CSA domovea basic certificate ↗Reviewed Nov 4, 2026