xxter
xxter Pairot
DIN-rail KNX-to-Matter bridge for lighting, shading, climate, access and room sensors.
- Product type
- KNX to Matter bridge
- Model / SKU
- Pairot
- KNX connection
- Direct KNX TP, or KNXnet/IP tunneling/routing
- Matter connection
- Ethernet
Matter functions & installation
This bridge exposes supported KNX functions to a Matter platform. Its configuration, firmware and supported endpoint types determine which controls and readings are available.
Documented Matter functions
- Lights including color and color temperature
- Switched sockets and switches
- Thermostats and fan control
- Blinds
- Door locks and push buttons
- Temperature, humidity, contact, illuminance, motion and presence sensors
Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.
Bridge setup: commands, readings and feedback
Match the ETS group objects to the selected bridge and receiving app. These examples explain configuration requirements; they do not establish compatibility with every bridge.
Switching and dimming
Configure commands and readable status feedback. 1Home requires absolute brightness values for percentage control; relative wall-button dimming alone is insufficient.
1Home instructions ↗Shades and blinds
Map movement, stop and position feedback. Slat adjustment needs matching objects. A timed-position fallback estimates position instead of measuring it.
1Home instructions ↗Climate and sensors
Keep measured temperature and humidity separate from setpoints. A valve output alone is not a complete thermostat. Atios documents the required group addresses for each accessory.
Atios instructions ↗Extra KNX values
1Home can display generic KNX data in its own app without exporting it to Matter. Do not assume that energy, wind, rain or diagnostic values appear in every Matter app.
1Home instructions ↗Technical specifications
KNX to Matter · ETS project import · Matter-to-KNX integration
- Matter export capacity
- 150
- Matter certificate
- CSA25272MAT45508-00
- Certified revision
- Hardware 1; firmware 2.0.0; Matter 1.4
- Commercial status
- Manufacturer provides professional ordering and distributor channels; current stock not checked.
Sources & limitations
Product research reviewed: Nov 4, 2026. This is separate from price, stock and installation-test dates.
Model, firmware & function limitations (6)
- Up to 150 exported KNX components.
- Support in individual Matter apps varies, particularly buttons, fan functions and blind tilt.
- Matter-to-KNX is documented but was marked beta in the firmware 2.0.0 release notes; verify the installed version before relying on the reverse path.
- Configuration uses My xxter; local Matter control should not be confused with completely offline initial commissioning.
- HomeKit's broader accessory list is not a list of Matter-supported accessories.
- CSA confirms Pairot firmware 2.0.0, hardware 1, as a Matter 1.4 bridge over Ethernet.
Manufacturer documentation & sources (5)
- Pairot Matter functions and capacity ↗Reviewed Nov 4, 2026
- CSA Pairot Matter certificate ↗Reviewed Nov 4, 2026
- Pairot installation manual: KNX connection options ↗Reviewed Nov 4, 2026
- Pairot Matter commissioning and reverse integration ↗Reviewed Nov 4, 2026
- Manufacturer release notes: Matter-to-KNX beta status ↗Reviewed Nov 4, 2026