JUNG KNX control unit 1 – 10 V, 4-gang, 16 A / 200 µF, rail mounting device, 4 rail units | KNX via Matter | BUILD10
BUILD10
Local Service PartnersAI PartnersProduct
About UsContact
BUILD10
← KNX via Matter catalogProject shortlist (0)
JUNG KNX control unit 1 – 10 V, 4-gang, 16 A / 200 µF, rail mounting device, 4 rail units 2194 REGHM

JUNG

JUNG KNX control unit 1 – 10 V, 4-gang, 16 A / 200 µF, rail mounting device, 4 rail units

KNX control unit 1 – 10 V, 4-gang, 16 A / 200 µF, rail mounting device, 4 rail units. KNX lighting controller for dimming compatible connected lamps or control gear.

Product type
Lighting & switching
Model / SKU
2194 REGHM
KNX connection
TP wired bus

Connecting this device to Matter

This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.

Functions to map through a bridge

  • Switched load / outlet
  • Lighting brightness and on/off

Selected native KNX functions can be mapped using a suitable Matter bridge. Additional probes, contacts, couplers, controlled equipment or temperature controllers may be required as described below. Exact device–bridge combinations have not been tested.

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.

Bridge options by function

These options match the product’s KNX functions to capabilities documented for a bridge. Open the bridge for its requirements and limitations.

1Home Voice & Visu

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

1Home Server KNX Pro

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Atios KNX Bridge

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Technical specifications

Switching · Dimming

KNX connection
TP wired bus
KNX medium
TP 256
Rated voltage KNX
DC 21 ... 32 V SELV
Current consumption KNX
max. 6 mA
Power loss
max. 4 W
Ambient temperature
−5 ... +45 °C
Storage/transport temperature
−25 ... +70 °C
Control voltage
1 ... 10 V
Control current per output
max. 100 mA
Cable length
max. 500 m (0.5 mm²)
Contact type
floating relay contacts (μ contact)
Switching voltage AC
AC 250 / 400 V
Switching current 230 V AC1
16 A
Switching current 230 V AC3
10 A
Switching current 400 V AC3
6 A
Switching voltage DC
DC 12 ... 24 V
Min. switching current
100 mA
Switch-on current 150 µs
600 A
Specifications with sources (17)

KNX medium

TP 256

View specification source ↗

Rated voltage KNX

DC 21 ... 32 V SELV

View specification source ↗

Current consumption KNX

max. 6 mA

View specification source ↗

Power loss

max. 4 W

View specification source ↗

Ambient temperature

−5 ... +45 °C

View specification source ↗

Storage/transport temperature

−25 ... +70 °C

View specification source ↗

Control voltage

1 ... 10 V

View specification source ↗

Control current per output

max. 100 mA

View specification source ↗

Cable length

max. 500 m (0.5 mm²)

View specification source ↗

Contact type

floating relay contacts (μ contact)

View specification source ↗

Switching voltage AC

AC 250 / 400 V

View specification source ↗

Switching current 230 V AC1

16 A

View specification source ↗

Switching current 230 V AC3

10 A

View specification source ↗

Switching current 400 V AC3

6 A

View specification source ↗

Switching voltage DC

DC 12 ... 24 V

View specification source ↗

Min. switching current

100 mA

View specification source ↗

Switch-on current 150 µs

600 A

View specification source ↗

Sources & limitations

Product research reviewed: Nov 5, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (2)
  • Requires a commissioned KNX installation, mapped group addresses and a KNX-to-Matter bridge that supports the selected function. Exact device/bridge pair not physically tested.
  • Exact model and KNX function identified in manufacturer documentation. Matter applicability is function-level and requires bridge configuration; not a tested pair.
Manufacturer documentation & sources (1)
  • JUNG — KNX control unit 1 – 10 V, 4-gang, 16 A / 200 µF, rail mounting device, 4 rail units ↗Reviewed Nov 5, 2026
← Back to resultsOpen project shortlist

© 2026 BUILD10

HomeRecommended DevicesContactPrivacy Policy