JUNG KNX multi station universal, rail mounting device, 8 rail units | KNX via Matter | BUILD10
BUILD10
Local Service PartnersAI PartnersProduct
About UsContact
BUILD10
← KNX via Matter catalogProject shortlist (0)
JUNG KNX multi station universal, rail mounting device, 8 rail units 2590 M1SR

JUNG

JUNG KNX multi station universal, rail mounting device, 8 rail units

Combined KNX room controller with lighting, shading, fan-coil, thermostat and external contact functions.

Product type
Lighting & switching
Model / SKU
2590 M1SR
KNX connection
TP wired bus

Connecting this device to Matter

This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.

Functions to map through a bridge

  • Switched load / outlet
  • Lighting brightness and on/off
  • Shades / blinds
  • Thermostat control
  • Fan control
  • Contact state

Selected native KNX functions can be mapped using a suitable Matter bridge. Additional probes, contacts, couplers, controlled equipment or temperature controllers may be required as described below. Exact device–bridge combinations have not been tested.

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.

Bridge options by function

These options match the product’s KNX functions to capabilities documented for a bridge. Open the bridge for its requirements and limitations.

1Home Voice & Visu

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off · Shades / blinds · Thermostat control · Contact state

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

1Home Server KNX Pro

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off · Shades / blinds · Thermostat control · Contact state

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Atios KNX Bridge

Function mapping, not a tested device–bridge pair

Switched load / outlet · Lighting brightness and on/off · Shades / blinds · Thermostat control · Fan control · Contact state

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Technical specifications

Switching · Dimming · Shading · Thermostat · Fan control · Door / window input

KNX connection
TP wired bus
Dimming outputs
4
Switch / blind outputs
10 / 5
Heating controllers
3
Rated voltage
AC 110/230 V ~
Mains frequency
50/60 Hz
Ambient temperature
−5 ... +45 °C
Storage/transport temperature
−25 ... +70 °C
Power loss
max. 14 W
Stand-by power
max. 0.55 W
Connected load
see operating instructions
Number of valve drives
max. 4 (230 V), 2 (110 V)
Control voltage
0 ... 10 V
Current carrying capacity
10 mA
Switching voltage
AC 230 V ~
Switching current
16 A
AX load
16 AX
External ballasts
16 A, 140 μF
Specifications with sources (14)

Rated voltage

AC 110/230 V ~

View specification source ↗

Mains frequency

50/60 Hz

View specification source ↗

Ambient temperature

−5 ... +45 °C

View specification source ↗

Storage/transport temperature

−25 ... +70 °C

View specification source ↗

Power loss

max. 14 W

View specification source ↗

Stand-by power

max. 0.55 W

View specification source ↗

Connected load

see operating instructions

View specification source ↗

Number of valve drives

max. 4 (230 V), 2 (110 V)

View specification source ↗

Control voltage

0 ... 10 V

View specification source ↗

Current carrying capacity

10 mA

View specification source ↗

Switching voltage

AC 230 V ~

View specification source ↗

Switching current

16 A

View specification source ↗

AX load

16 AX

View specification source ↗

External ballasts

16 A, 140 μF

View specification source ↗

Sources & limitations

Product research reviewed: Nov 5, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (3)
  • Requires a commissioned KNX installation, mapped group addresses and a KNX-to-Matter bridge that supports the selected function. Exact device/bridge pair not physically tested.
  • Outputs and inputs share resources; available functions depend on the ETS configuration. Sensors and loads are separate.
  • Exact model and KNX function identified in manufacturer documentation. Matter applicability is function-level and requires bridge configuration; not a tested pair.
Manufacturer documentation & sources (1)
  • JUNG — KNX multi station universal, rail mounting device, 8 rail units ↗Reviewed Nov 5, 2026
← Back to resultsOpen project shortlist

© 2026 BUILD10

HomeRecommended DevicesContactPrivacy Policy