JUNG KNX heating actuator, 6-gang with controller, rail mounting device, 4 rail units 36006 1S R

JUNG

JUNG KNX heating actuator, 6-gang with controller, rail mounting device, 4 rail units

KNX heating actuator, 6-gang with controller, rail mounting device, 4 rail units. Six-output KNX heating actuator with integrated temperature controllers for heating or cooling zones.

Product type
Climate
Model / SKU
36006 1S R
KNX connection
TP wired bus

Connecting this device to Matter

This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.

Functions to map through a bridge

  • Thermostat control

Selected native KNX functions can be mapped using a suitable Matter bridge. Additional probes, contacts, couplers, controlled equipment or temperature controllers may be required as described below. Exact device–bridge combinations have not been tested.

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.

Bridge options by function

These options match the product’s KNX functions to capabilities documented for a bridge. Open the bridge for its requirements and limitations.

1Home Voice & Visu

Function mapping, not a tested device–bridge pair

Thermostat control

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

1Home Server KNX Pro

Function mapping, not a tested device–bridge pair

Thermostat control

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Atios KNX Bridge

Function mapping, not a tested device–bridge pair

Thermostat control

Proposed from documented KNX and bridge function types. Verify the exact ETS application, required command/status objects, KNX Secure access and receiving-app support. This model–bridge pair has not been physically tested.

View mapping source ↗

Technical specifications

Thermostat

KNX connection
TP wired bus
Valve outputs
6
Room controllers
12
Valve supply
24 or 230 V AC
KNX medium
TP 256
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 32 V SELV
Current consumption KNX
4.5 ... 10 mA
Contact type
semiconductor (triac), ε
Switching voltage
AC 24 / 230 V ~
Mains frequency
50/60 Hz
Switching current
5 ... 160 mA
Switch-on current
max. 1.5 A (2 s)
Number of valve drives
max. 4 (230 V), 2 (24 V)
Mounting width
72 mm (4 rail units)
Ambient temperature
−5 ... +45 °C
Storage/transport temperature
−25 ... +70 °C
Connection mode
screw terminals
Specifications with sources (14)

KNX medium

TP 256

View specification source ↗

Commissioning mode

S-mode

View specification source ↗

Rated voltage KNX

DC 21 ... 32 V SELV

View specification source ↗

Current consumption KNX

4.5 ... 10 mA

View specification source ↗

Contact type

semiconductor (triac), ε

View specification source ↗

Switching voltage

AC 24 / 230 V ~

View specification source ↗

Mains frequency

50/60 Hz

View specification source ↗

Switching current

5 ... 160 mA

View specification source ↗

Switch-on current

max. 1.5 A (2 s)

View specification source ↗

Number of valve drives

max. 4 (230 V), 2 (24 V)

View specification source ↗

Mounting width

72 mm (4 rail units)

View specification source ↗

Ambient temperature

−5 ... +45 °C

View specification source ↗

Storage/transport temperature

−25 ... +70 °C

View specification source ↗

Connection mode

screw terminals

View specification source ↗

Sources & limitations

Product research reviewed: Nov 5, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (3)
  • Requires a commissioned KNX installation, mapped group addresses and a KNX-to-Matter bridge that supports the selected function. Exact device/bridge pair not physically tested.
  • Requires temperature feedback and valve drives. Export the complete configured thermostat zone, not an isolated valve output.
  • Exact model and KNX function identified in manufacturer documentation. Matter applicability is function-level and requires bridge configuration; not a tested pair.