Connecting this device to Matter
This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.
Functions to map through a bridge
Use complete room-control zones with measured temperature and setpoint, not raw valve outputs alone. The bridge must support the commissioned KNX Secure objects. The 0.25 A rating applies to each adjacent output pair, not each channel. No specific device–bridge pair has been tested.
Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.
Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.
Technical specifications
Heating · Cooling · Thermostat
- Order code
- 2CDG110331R0011
- Outputs
- 12 electronic valve outputs
- Valve supply
- 24–230 V AC, 50/60 Hz
- Current limit
- 0.25 A rated per adjacent output pair; 1.5 A maximum for device
- Security
- KNX Data Secure
- Mounting
- DIN rail, 8 modules / 140 mm
- Protection
- IP20; overload and short-circuit protection
- Commercial status
- Stock, destination-specific delivery and current USD price have not been verified.