Connecting this device to Matter
This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.
Functions to map through a bridge
Export a configured temperature-control zone, with room temperature, target temperature and supported mode feedback. A raw valve output alone is not a complete thermostat. KNX protection, demand logic and all comfort modes are not automatically exposed. No specific device–bridge pair has been tested.
Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.
Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.
Technical specifications
Heating · Cooling · Thermostat
- Outputs
- 8
- Valve voltage
- 24–230 V AC
- Room control
- Integrated PI controller per channel; external room-temperature measurement required
- Actuators per channel
- Up to 4 at 230 V AC or 3 at 24 V AC
- Control input
- 1-bit switching/PWM, 1-byte value or KNX room temperature
- Mounting
- DIN rail, 4 modules
- Commercial status
- Stock, destination-specific delivery and current USD price have not been verified.