Theben thePrema P360 KNX UP WH | KNX via Matter | BUILD10
BUILD10
Local Service PartnersAI PartnersProduct
About UsContact
BUILD10
← KNX via Matter catalogProject shortlist (0)
Theben thePrema P360 KNX UP WH 2079000

Theben

Theben thePrema P360 KNX UP WH

Ceiling KNX PIR presence detector with square coverage and separate lighting and HVAC-presence channels.

Product type
Sensors & inputs
Model / SKU
2079000
KNX connection
KNX TP

Connecting this device to Matter

This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.

Functions to map through a bridge

  • Illuminance
  • Occupancy

This is a KNX device, not a native Matter product. Export requires a KNX-to-Matter bridge, ETS group-address configuration and support for the chosen Matter device type. This exact device/bridge combination has not been tested. Select the intended presence channel and light measurement in ETS. Constant-light control, master/slave logic and local timing remain KNX functions unless explicitly implemented by the bridge.

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.

Bridge options by function

These options match the product’s KNX functions to capabilities documented for a bridge. Open the bridge for its requirements and limitations.

1Home Voice & Visu

Function mapping, not a tested device–bridge pair

Illuminance · Occupancy

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

1Home Server KNX Pro

Function mapping, not a tested device–bridge pair

Illuminance · Occupancy

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

Atios KNX Bridge

Function mapping, not a tested device–bridge pair

Illuminance · Occupancy

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

xxter Pairot

Function mapping, not a tested device–bridge pair

Illuminance · Occupancy

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

Technical specifications

Presence · Illuminance

Detection
360° PIR
Coverage at 3 m mounting height
9 × 9 m walking; 7 × 7 m seated
KNX channels
3 lighting channels; 2 presence channels
Mounting
Flush-mounted ceiling
Ambient temperature
0–50 °C
Protection
IP40 when fitted
Finish
White
Commercial status
Stock, destination-specific delivery and current USD price have not been verified.
Detection angle
360°
Installation type
Ceiling installation, Flush-mounted
Detection range
81 m² (9 x 9 m)
Colour
White (similar RAL 9010)
Specifications with sources (4)

Detection angle

360°

View specification source ↗

Installation type

Ceiling installation, Flush-mounted

View specification source ↗

Detection range

81 m² (9 x 9 m)

View specification source ↗

Colour

White (similar RAL 9010)

View specification source ↗

Sources & limitations

Product research reviewed: Nov 4, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (1)
  • Select the intended presence channel and light measurement in ETS. Constant-light control, master/slave logic and local timing remain KNX functions unless explicitly implemented by the bridge.
Manufacturer documentation & sources (1)
  • Theben thePrema P360 KNX UP WH — official product page ↗Reviewed Nov 4, 2026