Theben HMG 6 T KNX Heating Actuator 4930240

Theben

Theben HMG 6 T KNX Heating Actuator

Six valve-control channels with integrated room controllers for hydronic heating and cooling.

Product type
Climate
Model / SKU
4930240
KNX connection
KNX TP

Connecting this device to Matter

This product uses KNX. A compatible bridge can expose selected functions to Matter through its IP connection. The KNX device itself does not become a Matter over Thread device.

Functions to map through a bridge

  • Thermostat control

Requires room-temperature data and a commissioned control zone. Map setpoint, measured temperature and supported heat/cool modes. Check valve quantities and grouped current limits before specifying loads. No specific device–bridge pair has been tested.

Commission the KNX installation in ETS, then configure the bridge with the required group addresses, data types and status feedback. Check the exact bridge firmware and your Matter platform. Native KNX functions, electrical ratings and Matter functions are separate specifications.

Function mapping is not a tested device–bridge pair or individual Matter certification for this KNX model. Protection functions and essential local automation should remain in the KNX installation.

Bridge options by function

These options match the product’s KNX functions to capabilities documented for a bridge. Open the bridge for its requirements and limitations.

1Home Voice & Visu

Function mapping, not a tested device–bridge pair

Thermostat control

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

1Home Server KNX Pro

Function mapping, not a tested device–bridge pair

Thermostat control

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

Atios KNX Bridge

Function mapping, not a tested device–bridge pair

Thermostat control

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

xxter Pairot

Function mapping, not a tested device–bridge pair

Thermostat control

The bridge documents these function types. Commission the required KNX command and feedback objects in ETS, then map them in the bridge. Exact model pairing has not been tested; receiving-app support must also be checked.

View mapping source ↗

Technical specifications

Heating · Cooling · Thermostat

Product designation
HMG 6 T KNX
Included channels
6; six P/PI room controllers
Valve voltage
24–240 V AC
Output rating
Triac outputs, 0.45 A; observe grouped-load limits in the documentation
Supply
110–240 V AC, 50/60 Hz
Expansion
Up to 18 channels with two optional modules
Mounting
DIN rail, 4 modules
Commercial status
Stock, destination-specific delivery and current USD price have not been verified.
KNX bus current
≤4 mA
Switching output
Not potential-free
Output
Triac, 0.45 A
Voltage output
24 V AC - 240 V AC
Ambient temperature
-5°C ... 45°C
Type of protection
IP 20
Protection class
II according to EN 60 669
Specifications with sources (7)

KNX bus current

≤4 mA

View specification source ↗

Switching output

Not potential-free

View specification source ↗

Output

Triac, 0.45 A

View specification source ↗

Voltage output

24 V AC - 240 V AC

View specification source ↗

Ambient temperature

-5°C ... 45°C

View specification source ↗

Type of protection

IP 20

View specification source ↗

Protection class

II according to EN 60 669

View specification source ↗

Sources & limitations

Product research reviewed: Nov 4, 2026. This is separate from price, stock and installation-test dates.

Model, firmware & function limitations (1)
  • Requires room-temperature data and a commissioned control zone. Map setpoint, measured temperature and supported heat/cool modes. Check valve quantities and grouped current limits before specifying loads. No specific device–bridge pair has been tested.
Manufacturer documentation & sources (1)
  • Theben HMG 6 T KNX specifications ↗Reviewed Nov 4, 2026